null

6 Gallon Tempering Valve

$840.00
SKU:
AO-125389
Share Product:
Write a Review

Want to learn more or need help deciding?

Request More Info or call 1-888-312-8262

Application

Tempering valve to blend hot and cold water to deliver tepid water. Valve has flow capacity of 0.5 to 6 gallons per minute (GPM). Valve can be used with eyewash, eye/face wash, dual purpose eyewash/drench hose and drench hose units.

Temperature Control

Valve has bimetallic thermostat that senses incoming water temperature and automatically blends water to 85°F (29°C). High temperature limit stop is set to 90°F (32°C). Valve has dial thermometer on outlet to monitor temperature of delivered water. Note: Valve may need to be adjusted when installed based on incoming water temperature. Refer to “Installation Instructions” for further information.

Fail Safe

In event of restriction or failure of hot water supply, internal bypass allows valve to deliver cold water to emergency unit. In bypass mode, valve will deliver 4 GPM of cold water at 30 PSI flow pressure. In event of loss of cold water supply, valve will close and not deliver water.

Flow Capacity

System Pressure Drop (PSI) 5 10 15 20 25 30 35 40
Flow Rate (GPM) 2.0 2.7 3.5 4.5 5.5 6.5 7.5 8.5

System Pressure Drop (BAR)
.3 .7 1.0 1.4 1.7 2.1 2.4 2.8
Flow Rate (Liters per Minute) 7.6 10 13 17 21 25 28 32

Supply Temperature

Minimum hot water supply temperature is 140°F (60°C).

Supply Pressure

30 PSI minimum supply pressure is required for proper operation of valve. Maximum supply pressure is 125 PSI. Maximum hot to cold water pressure differential is 5%.

Mounting

Furnished with heavy duty mounting bracket for securing valve to panel or wall.

Inlets

1/2" nominal sweat female hot and cold water inlets. Each inlet has check valve and supply stop.

Outlet

1/2" NPT female outlet.

Quality Assurance

Valve is completely assembled and water tested prior to shipment. Unit is certified to ASSE 1071. Valve is certified to meet low lead requirements of wetted surface area less than 0.25% lead by weight.


Important: Pursuant to ANSI Z358.1-2014, the water delivered by emergency equipment should be “tepid”. Tepid is defined as moderately warm or lukewarm, and is generally considered to be between 60°F (15°C) and 90° (32°C). However, in certain circumstances, a chemical reaction may be accelerated or otherwise affected by the water temperature. Please consult with a medical advisor to determine the optimum delivered water temperature prior to specifying, installing or using a tempering valve.

Tempering valves will not deliver the appropriate water temperature if the system has not been sized correctly. Please refer to the flow capacities and supply pressure requirements listed above when designing the tempered water system and selecting tempering valves.

Tempering valves, like all emergency eyewash and shower equipment, must be installed in accordance with the manufacturer’s instructions and maintained on a regular basis. Under ANSI Z358.1-2014, all emergency equipment should be activated weekly and inspected at least annually. Tempering valves should be treated the same and, in addition, must be regularly cleaned and cycled.


Customers Also Viewed

Secure Checkout Including
All Major Credit Cards

Great Pricing & Convenient Ordering
Through Our GSA Contract

Learn More

Reliable Shipping
& Order Tracking

Learn More

Need help? we're available
to assist your needs

Contact Us
 

Question on a Product or Order?

We're happy to answer questions or help you.

Contact Us

Need a Custom Quote?

We engineer and source products for our customers.

Request Quote

Want to Partner With Us?

We partner with many suppliers in our industry.

Request Partnership